Тех. данные
Дизайн
- Connection of 24 V power supply
- Connection of solid-state relays via front plug
- Connection of external current measuring module
- Connection of voltage feedbacks from the load circuits
- Connection of phases L1, L2, L3 and zero conductor via busbars
(only required with voltage diagnostics)
Функции
Output power
- 24 channels with a digital 24-V control signal (8 outputs per phase)
- Max. 20 kW switching capacity with 230 V or 36 kW with 400 V per output
Monitoring of supply voltage
The connected 24-V supply is monitored for failure. The outputs to the solid-state relays are switched off in the event of a failure.
The drivers of the control outputs are monitored for correct functioning.
Fuses
External fuses must be provided for each channel.
Diagnostics facilities
Two different diagnostics methods are possible as alternatives:
- The following faults can be detected by diagnostics of the voltages from the load circuit:
- SSR cannot be switched on, interruption in line to SSR, or external channel fuse blown
- SSR cannot be switched off, interruption in heat emitter or line
- The following faults can be detected in addition by diagnostics using the external current measuring module:
- Rated power on channel exceeded
- Rated power on channel fallen below
This diagnostics is recommended for fault detection with radiators connected in parallel.
Технические данные
LA 724i SSR power output module
|
Outputs per load control (LA 724i SSR)
|
24
|
Electrical isolation from control unit
|
By optocoupler specified according to VDE 0884
|
Insulation voltage of optocoupler
|
5.3 kV
|
Electrical isolation between diagnostics inputs
|
No
|
Diagnostics voltage (for star and delta connections)
|
|
|
230 V AC / 400 V AC
|
|
187 V ... 264 V / 340 V ... 460 V
|
|
50 Hz/60 Hz (47 Hz ... 63 Hz)
|
Total current per phase and module
|
See current measuring module
|
Current per busbar
|
Max. 120 A
|
24 V power supply for control of SSR
|
|
|
24 V
|
|
20.4 V ... 28.8 V
|
|
1.5 A/250 V fast-blow (external)
|
Control voltage
|
24 V
|
|
Typ. 23.3 V
Min. 22 V
|
Control current
|
Max. 50 mA per control output
|
Line lengths
|
|
|
Max. 30 m
|
|
Max. 30 m
|
|
Max. 10 m
Note:
routing of lines not outside buildings
|
Dimensions of LA 724i SSR
(W x H x D)
|
50 mm x 480 mm x 210 mm
|
Weight, approx.
|
3.3 kg
|
Дополнительно
Order No.
|
Description
|
6BK1 700 ‑ 2BA40 ‑ 0AA0
|
SM 724i current measuring module
|
Part No. A5E00210675
|
Mating connector for 24 V power supply
|
Part No. A5E00043661
|
Mating connector for connection of SSR
(3 required per LA)
|
Part No. A5E00210670
|
Mating connector for connection of current measuring module
|
Part No. 41818384
|
Mating connector for voltage diagnostics
(3 required per LA)
|
6ES7 171 ‑ 3AA00 ‑ 0AA0
|
Fan module for HS 724
Required with powers greater than 650 Watt per channel on LA 724
|
6ES7 171 ‑ 2XX00 ‑ 6DA0
|
Heater control busbar,
only required with voltage diagnostics
|
Recommendations for solid-state relays
SIRIUS SC semiconductor relays/contactors, e.g. 3RF2350‑1AA02:
semiconductor protection 50 A, 40 °C, control voltage 24 V, screw connection
Дальнейшая информация
Ordering location
|
New parts and accessories
|
Siemens AG A&D SE FTH
|
Org-ID 10001539
|
Repairs
|
Siemens AG A&D SE EWF RC Fürth
|
Org-ID AV000085
|